王浩 王利國


【摘要】 本文介紹了用交流采樣校驗裝置檢定多功能電力儀表測量結果的不確定度評定方法,為以后測量交流采樣類儀表的不確定度評定提供參考。
【關鍵詞】 多功能電力儀表;交流采樣校驗裝置;不確定度
【DOI編碼】 10.3969/j.issn.1674-4977.2021.04.010
Uncertainty Evaluation of Measurement Results of AC Sampling Calibration Device
WANG Hao1,WANG Li-guo2
(1.Anshan Institute of Metrology Supervision and Verification,Anshan 114000,China;
2.Panjin Metrological Testing and Standardization Research Service Center,Panjin 124000,China)
Abstract: This paper introduces the evaluation method of uncertainty of measurement results of multi-functional power instruments verified by AC sampling calibration device,which provides a reference for the evaluation of uncertainty of measurement of AC sampling instruments in the future.
Key words: multi function power meter;AC sampling calibration device;uncertainty
1 概述
1)測量依據:JJF(遼) 344-2016《交流采樣測量裝置校準規范》;2)環境條件:溫度:20.6 ℃,相對濕度:53%RH;3)測量標準:交流采樣校驗裝置,BD-3H3;4)被測對象:多功能電力儀表,型號A60;5)測量過程:采用直接測量法測量,將交流采樣校驗裝置與被校多功能電力儀表直接連接,由交流采樣校驗裝置輸出信號給多功能電力儀表。
2 建立測量模型和傳播律
2.1 測量方法
按照JJF(遼) 344-2016《交流采樣測量裝置校準規范》中的要求,將交流采樣校驗裝置與被校多功能電力儀表正確連接,根據校準規范規定的檢測點依次進行測量。
2.2 測量模型
[γ=γ0]
式中:[γ]——被測多功能電力儀表示值;
[γ0]——交流采樣校驗裝置輸出標準值。
2.3 傳播率
[uc2(γ)=c2uc2(γ0)]
式中靈敏系數為:[c=?γ?γ0=1]。
3 標準不確定度分量評定
3.1 重復測量引起的不確定度評定
由重復性引入的不確定度分量采用A類評定。以測量A60型號的多功能電力儀表為例,重復測量10次。數據如表1。
單次測量標準偏差為:
[u1U=0.00995] V
3.2 被測儀表分辨力引起的不確定度分量的評定
[u2U=0.0123=0.00289] V
由于分辨力引入的不確定度分量小于重復性引入得不確定度分量,所以舍去,只考慮由重復性引入得不確定度分量。
3.3 標準器交流采樣校驗裝置引入的不確定度分量的評定
標準器交流采樣校驗裝置引入的不確定度分量的評定結果見表2。
3.4 標準不確定度匯總
標準不確定度匯總結果見表3。
4 合成標準不確定度的評定
以上各項標準不確定度分量是互不相關的,所以合成標準標準不確定度為:
[ucγ=u1U2+u3U2]
合成標準不確定度結果見表4。
5 擴展不確定度評定
取包含因子k=2,則:[U=k×ucγ]。擴展不確定度結果見表5。
其他參數參照上述評定如下:電流:UrI=0.9×10-3(5 A);功率:UrP=0.6×10-3(1100 W);功率因數:UrPF=1.6×10-3(1);頻率:UrF=0.6×10-3(50 Hz)。
6 結語
本文介紹的不確定度評定方法,同樣適用于數字式交流電參數測量儀,數字顯示的多功能測量儀器的交流電參數部分的測量結果的不確定度評定。
【參考文獻】
[1]??? 測量不確定度評定與表示:JJF 1059.1-2012[S].
[2]??? 交流采樣測量裝置校準規范:JJF(遼) 344-2016[S].
【作者簡介】
王浩(1989-),男,學士,研究方向為電磁量、時間頻率的計量檢測。
王利國(1991-),男,學士,研究方向為電磁量的計量檢測。