999精品在线视频,手机成人午夜在线视频,久久不卡国产精品无码,中日无码在线观看,成人av手机在线观看,日韩精品亚洲一区中文字幕,亚洲av无码人妻,四虎国产在线观看 ?

Design and realization of signal acquisition digital system for leak detection of water supply pipeline*

2014-06-04 11:15:10HongliLYUCuiyingDONG
機(jī)床與液壓 2014年12期

Hong-li LYU,Cui-ying DONG

Department of Information Engineering,Tangshan College,Tangshan 063000,China

1.Introduction

As far as urban water supply system is concerned in our country,the leakage of water supply pipeline could cause serious water loss at each year[1].Therefore,how to develop the instruments for pipeline to monitor and position the leakage is a new promising research subject.Since the data used to detect the pipeline leakage have a direct impact on the leakage position accuracy for the pipeline,the data acquisition system becomes very important to determine the leakage position of pipeline[2-4].

2.Theory of correlation detection of pipeline leakage

The schematic diagram of correlation detection is shown in Figure 1[5-6].The leakage signal travels in two directions with the velocityv.The symbolL1andL2stand for the distance from 1#and 2#sensor to the leakage position.The time difference of the signal arrival the two sensors is called time delay and is symbolizedD.The distance between the two consecutive sensors is symbolized asL.According to the similarity of the two signals,the peak value of correlation function could be obtained and the time delayDcould be evaluated and then the leakage position could be is determined.The distance from leakage position to 1#sensor isL1and it could satisfy the following formula.

Figure 1.The principle of correlation detection

3.Control scheme for signal acquisition system

Due to the different material of pipeline,diameter of pipeline and shape of leakage position,the frequency distribution of leakage signal could vary in a relative big range.The frequency range of water leakage sound signals for the metal pipeline is from 500 Hz to 3 500 Hz[7].Since the water leakage signal is transmitted through soil to ground,the amplitude of this signal could be decreased.Based on the on-site field measurement,the frequency range of leakage sound is always between 100 Hz and 700 Hz which could be detected from the ground.Therefore,the accelerometer is needed in the system to measure the vibration signal.According to the principle of correlation detection,the signal acquisition system should simultaneously obtain these two signals.

Since the obtained signals from the two sensors are weakened and there exist some noise signals,the signal adjustment circuit is designed to amplify and filter the noise signals.And then the signals will be converted into digital signals through the A/D chip and these digital signals could be saved by singlechip microcontroller(SCM).Because there exist some distance between the consecutive two sensors and various signals are stored by the main SCM,the data transmission is necessary and it is selected as RS-485.In order to obtain the real-time analysis for this system,a DSP chip is adopted to realize the complex algorithm for correlation detection theory and the RS-485 is used for the data transmission between the main SCM and DSP.The control scheme diagram for signal acquisition system is shown in Figure 2.

Figure 2.The system control scheme diagram

4.Design of the signal adjustment circuit

The signal adjustment circuit consists of amplification circuit and filter circuit.

4.1.Design of the signal amplification circuit

The leakage signal has relatively high dynamic range and is seriously affected by the outside environment.If the fixed-gain amplifier is adopted for the signal acquisition system,there exist some problems for the signals such as insufficient amplification or saturated amplification.Therefore,the adjustablegain amplifier should be selected and the dynamic gain range is between 0 dB and 32 dB.As shown in Figure 3,it is presented the signal amplification circuit with the chip NE5532,and the gain of this circuit could be adjusted by modulating the resistance value of R4.

Figure 3.Signal amplifying circuit with NE5532

4.2.Design of the signal filter circuit

The maximum limit of high frequency components for leakage signal is 3 500 Hz and the frequency bandwidth of noise is relatively wide,therefore the low pass filter is needed for the design of the filter circuit.Since the elliptic filter is one of the low pass filters and it has the minimal pass-band and stopband ripple as compared with other filters,this kind of filer is adopted in this paper.As shown in Figure 4,the elliptic filter circuit with chip LTC1068 is presented and the cut-off frequency is 3 500 Hz and the pass-band gain is 0 dB.

Figure 4.Signal filtering circuit

4.3.Hardware design for low noise and low power consumption

The signal amplification circuit could magnify the output signal of the sensor;however,at the same time the noise could be produced.In order to control the noise signal and prevent the signal pollution during the amplification process,the low noise components is selected for the circuit design,such as metal film resistor,field-effect tube,Rail-to-Rail device for integrated operational amplifier.

In order to adapt to the water pipeline leakage detection of outdoor working environment,the signal acquisition system is needed to be powered by a battery.Therefore,the system has the requirement for the low power consumption.Due to this reason,the SCM is selected to be the processor because it has relatively low power consumption characteristics as compared with other embedded processors.In addition,the low power devices meet the requirements for the design of the peripheral circuit and Lithium-ion battery of high energy density could be used in the real industrial applications.

5.Software design

After power on and initialization,the two SCM will wait for the instructions from the main SCM through RS-485 bus.Once the data acquisition instruction is received,the A/D chip will get started and the leakage signals could be obtained and saved.The saved data will be transmitted to DSP through RS-485 bus.The program flow chart of main SCM is illustrated in Figure 5.

Figure 5.Program flow chart of data acquisition system

6.Conclusion

The leakage signals are simulated by signal generator and the peak-to-peak voltage amplitude is 500 mV and frequency is 1000 Hz.These signals will be adopted as the input signals for the signal adjustment circuit.The peak-to-peak voltage amplitude of output signals from adjustment circuit is 4 V.As shown in Figure 6,it is presented the input and output simulated waveforms for signal adjustment circuit.This demonstrates that the magnification factor of signal amplification circuit is eight.

Figure 6.The input and output simulated waveform of signal adjust circuit

Figure 7 is the model machine of signal acquisition system and Figure 8 is the waveform recorded in the field testing for water pipeline leakage.The data stored in SCM is transmitted to DSP by RS-485 and the complex filtering algorithm and localization algorithm are achieved by DSP.

Figure 7.The signal acquisition system prototype

Figure 8.The waveform recorded in the field testing

The designed leakage signal acquisition system has low noise and low power consumption.It is capable to match the outdoor working environment for leakage detection and could be applied to the petroleum,gas or other pipelines.

[1]Qian Yi,Liu Changming.Sustainable development of water resource in Chinese urban[M].Beijing:China Water Power Press,2002.

[2]Wang Ji-hua,Peng Zhen-bin,Guan Xiang-feng.Leakage testing techniques and prospect for ductwork of water supply[J].Journal of Guilin institute of technology,2004,24(4):456-460.

[3]Pilcher R,Hamilton S,Chapman H,et al.Leakage location & repair guidance notes version 1[J].Water Loss Task Force,IWA.2007(3):12-18.

[4]Shu Shi-hu,He Wen-jie,et al.Current Application and Recent Development of Leakage Detection Technologies in Water Supply Networks[J].Journal of water &wastewater engineering,2008,34(6):114-116.

[5]Brennan M J,Gao Y,Joseph P F.On the relationship between time and frequency domain methods in time delay estimation for leak detection in water distribution pipes[J].Journal of Sound and Vibtation,2007,304:213-223.

[6]Gao Y,Brennan M J,Joseph P F,et al.On the selection of acoustic/vibration sensors for leak detection in plastic water pipes[J].Journal of Sound and Vibtation,2005,283:927-941.

[7]Feng Ying-jian.Research on leakage detection system of city water pipeline[D].Shenyang:Shenyagn University of Technology,2008.

主站蜘蛛池模板: 久久精品视频一| 国产免费怡红院视频| 人妻一本久道久久综合久久鬼色| 99热这里只有精品免费国产| 婷婷六月色| 国产在线小视频| 久综合日韩| 国产精品尹人在线观看| 人妻中文久热无码丝袜| 国产视频 第一页| 超碰91免费人妻| 白浆视频在线观看| 国产精品福利在线观看无码卡| 国产黄网站在线观看| 久久综合干| 久久久久国色AV免费观看性色| 免费99精品国产自在现线| 乱码国产乱码精品精在线播放| 日韩第一页在线| 91国内外精品自在线播放| 亚洲中文字幕在线观看| 四虎永久免费网站| 国产小视频网站| 国产精品无码作爱| 国产精品久久久久无码网站| 免费a级毛片视频| 国产一级毛片网站| 亚洲欧美精品日韩欧美| 国产在线视频自拍| 91久久精品日日躁夜夜躁欧美| 婷婷综合色| 国产97视频在线| 欧美α片免费观看| 精品一区二区久久久久网站| 亚洲大尺码专区影院| 日韩欧美国产三级| 日本在线视频免费| 国产丝袜无码一区二区视频| 99资源在线| 伊人久久影视| 国产精品久久久免费视频| 色偷偷av男人的天堂不卡| 精品国产黑色丝袜高跟鞋| 精品国产成人a在线观看| 中文字幕无线码一区| 亚洲永久色| 亚洲伦理一区二区| 国产二级毛片| 亚洲精品久综合蜜| 国产福利观看| 亚洲全网成人资源在线观看| 日本午夜影院| 亚洲日韩高清在线亚洲专区| 99re精彩视频| 国产在线八区| 欧美午夜在线观看| 国产极品美女在线播放| 免费a在线观看播放| 亚洲无码37.| 久久一本日韩精品中文字幕屁孩| 国产天天色| 狠狠干综合| 高潮毛片免费观看| 久久婷婷色综合老司机| 日韩av资源在线| 国产免费福利网站| 国产三级韩国三级理| 亚洲乱码精品久久久久..| 亚洲人成在线免费观看| 在线精品视频成人网| 午夜不卡福利| 国产亚洲精品91| 亚洲欧洲日本在线| 国产在线一区视频| 欧美一级99在线观看国产| 国产欧美精品一区二区| 99无码熟妇丰满人妻啪啪| 日韩国产欧美精品在线| 婷婷激情五月网| 成人亚洲视频| 国产 在线视频无码| 91成人在线观看视频|