傅俊萍+劉哲宇+何葉從+石沛



摘 要:當室外氣溫較高時,風冷熱泵系統冷凝器存在換熱效果下降的問題,而蒸發式冷凝器可以改善此問題,蒸發式冷凝器因此逐步得到廣泛重視。為研究采用蒸發式冷凝器制冷系統的能耗情況,通過正交實驗的方法,對比研究了蒸發式冷凝器與風冷式冷凝器在相同工況下壓縮機能耗情況,并對影響其性能的因素進行了分析。研究表明,各因素對壓縮機耗功量的影響能力依次為:冷凝器進口空氣溫度、速度及冷凝器噴水量。壓縮機耗功量隨進口空氣溫度的升高、進風空氣速度降低而增大,隨噴水量增加存在先減小后保持不變的現象。
關鍵詞:冷凝器;能耗分析;節能;傳熱傳質
中圖分類號:TU831.4 文獻標志碼:A 文章編號:1674-4764(2018)01-0129-05
Experimental analysis on energy consumption of air-conditioning evaporative condenser
Fu Junping, Liu Zheyu, He Yecong, Shi Pei
(College of Energy and Power Engineering, Changsha University of Science and Technology, Changsha 410114, P. R. China)
Abstract:The heat transfer efficiency of air-cooled heat pump system would decrease in high outdoor temperature. Evaporative condenser gradually get wide attention due to its contribution to solve the problem. In order to study the energy consumption of heat pump with evaporative condenser, it was made a comparative study about compressor power consumption of evaporative condenser and air cooling condenser under the same conditions by orthogonal experiment and analyzed factors of efficiency. The results show that the influence of factors on power consumption and energy efficiency of compressor are as follows: inlet air temperature of condenser water volume, air velocity. Compressor power consumption increases with the increase of inlet air temperature and the decrease of air velocity. The compressor energy consumption decreases at first and then is constant with the increase of water volume.
Keywords:condenser;energy consumption analysis ; energy saving;heat and mass transfer
風冷式冷凝器熱泵系統組成簡單,性能穩定可靠 [1],是空調系統中廣泛使用的一種設備。但當室外氣溫升高時,風冷式冷凝器的散熱環境變差,導致壓縮機耗能增大。蒸發式冷凝器因換熱效率高,并具有節能、節水、結構緊湊等優勢,在暖通空調行業越來越受到關注。
Ala等[2]通過實驗研究發現,在蒸發式冷凝器中翅片管束比光管管束傳遞熱量多92%~140%。Hosoz等[3]、莊友明[4]、王少為等[5]、張建一等[6]、王軍等[7]通過實驗發現,蒸發式冷凝器系統能耗比風冷式、水冷式少31%和14.3%。Ertunc等[8-9]利用神經網絡系統建立了蒸發式冷凝器系統性能的預測模型。Vrachopoulos等[10]、Wang等[11]、Liu等[12]分別通過整合蒸發式冷凝系統發現,降低壓縮機的操作溫差,系統性能系數最大可提高211%,利用蒸發冷卻式冷凝器預冷空氣,系統COP從6.1%增加至18%,壓縮機的能耗降低了14.3%。朱冬升等[13]、李元希等[14]研究了噴淋水蒸發式冷凝器傳熱傳質性能,發現噴淋密度滿足最小值時,改變噴淋密度對其傳熱傳質性能影響不大。高煌等[15]、葉軍等[16]通過實驗研究得出了蒸發式冷凝器傳熱系數的擬合經驗關系式。李元希等[17-18]對板式蒸發式冷凝器進行了傳熱性能的實驗研究,發現板式蒸發式冷凝器存在最佳入口風速和噴淋密度。
在對蒸發式冷凝器的已有研究中,由于側重點不同以及實驗條件各異,研究結果通用性不強。而且,蒸發式冷凝器性能受多種因素的影響,空氣參數及噴淋水參數是其中的兩個重要因素。參數值選取不當或者風量與水量間的配比關系不合理,都會對蒸發式冷凝器的換熱效果產生很大影響。為深入研究噴水量、進風溫度、進風速度等參數的耦合情況對蒸發式冷凝器壓縮機能耗的影響,筆者設計并搭建了風冷蒸發式冷凝器換熱實驗平臺,并在風冷式翅片管冷凝器設計的基礎上,增加了噴淋裝置,構成風冷式與蒸發式兩用型冷凝器換熱性能實驗系統。
1 實驗系統
實驗系統主要由空氣處理系統、空調制冷系統、噴淋水系統以及相關測試設備組成,如圖1所示。空氣處理系統主要由變頻風機、表冷器、電加熱器、加濕裝置和測量儀器組成,通過對各設備進行綜合調節控制,提供實驗段入口所需的空氣參數。空調制冷系統主要由蒸發器、冷凝器、壓縮機組成,壓縮機最大輸入功率1 900 W,吸排氣側最高壓力4.2 MPa,冷凝器的換熱面積為15.19 m2。蒸發器置于保溫密閉性能很好的人工環境室中,并在環境室內放置恒定功率的熱源,用以模擬房間熱負荷。噴淋水系統則是為蒸發式冷凝器提供水源,主要由膨脹水箱、變頻加壓水泵、噴嘴、布水管道以及相關測試儀器等設備組成,其中,由膨脹水箱出來的自來水經變頻水泵加壓后,經管道至噴嘴均勻噴灑到冷凝器上表面,噴嘴之間間距為102.5 mm,噴嘴與冷凝器的距離為80 mm時,冷凝器水膜分布較均勻。蒸發式冷凝器噴淋水系統如圖2所示。endprint
2 實驗結果與分析
2.1 空調用蒸發式冷凝器能耗正交實驗研究
影響蒸發式冷凝器性能的因素主要有:噴水量、噴水溫度、進風溫度、空氣進口相對濕度、進風速度、制冷劑流量、制冷劑溫度、蒸發器的主體結構和表面狀況等。實驗中,由于噴淋水的作用,使得空氣流到蒸發式冷凝器進口附近時濕度增加很大,而空氣濕度的變化對蒸發式冷凝器的換熱影響不大。蒸發式冷凝器的制冷劑流量和溫度,蒸發器的主體結構和表面狀況對冷凝器的換熱系數均有一定的影響,但上述因素在風冷式空調系統設計時均已考慮,因此,不做為本次實驗研究的重點。綜上原因,在影響蒸發式冷凝器性能的因素中,主要考慮:進風溫度、進風速度、噴水量3個因素。噴淋水直接采用長沙地區夏季自來水,水溫為23 ℃,實驗中取相對濕度60%。運用正交實驗法確定冷凝器進口空氣溫度、速度、噴水量3個因素的最佳水平以及對換熱性能的影響。正交實驗因素水平如表1所示,選用正交實驗表L9(34)安排實驗,壓縮機節能效率φ可由式(1)計算得出。
式中:φ為節能效率,%;W1為不噴水時壓縮機耗功量,W;W2為噴水時壓縮機耗功量,W。
通過直接觀察表2中的實驗指標,可知實驗序號3即進風溫度為1水平、進風速度為3水平、噴水量為3水平時,蒸發式冷凝器耗功量最小,為418 W。同時,發現實驗序號5即進風溫度為2水平、進風速度為2水平、噴水量為3水平時,蒸發式冷凝器節能效率最大,為36.92%。
以各因子的水平為橫坐標,壓縮機耗功量為縱坐標,繪制直觀分析趨勢圖,如圖4所示。
從圖4可以看出,壓縮機耗功量隨著進風溫度的升高或者噴水量的減小而增大;而隨著進風速度的增大,壓縮機耗功量先減小后增大,可見,風速并不是越大越好,而是存在一最佳風速值。
為了進一步分析各因素對冷凝器換熱性能的影響程度,運用方差分析法對正交實驗結果進行了分析,如表3所示。
由表3可知,進風速度的離差平方和小于誤差的離差平方和,進風速度對實驗指標影響較小,因而將進風速度項歸入誤差進行分析。通過計算得到的F值與F檢驗的臨界值比較可知,影響壓縮機耗功量的因素主次關系依次為:進風溫度、噴水量、進風速度,這與直觀分析得到的結論一致。
2.2 空調用蒸發式冷凝器能耗單因素實驗研究
由2.1內容可知,啟用噴淋裝置比不啟用噴淋裝置更加節能,而且,各因素的最佳水平分別為:進風溫度33 ℃、進風速度2.5 m/s、噴水量22 L/h,各最佳水平組合時節能效率最大,達36.92%。 分別對噴水量、進風溫度、進風速度3個因素進行了單因素實驗,即保持其他兩個因素條件不變,只改變另外一個因素的值進行實驗。實驗結果如圖6所示。
由圖4(a)可知, 同樣條件下,啟用噴水裝置比不啟用噴水裝置時壓縮機耗功量少,且隨著噴水量的增加,壓縮機耗功量從594 W減小到451 W后保持不變,這是因為,冷凝器上覆蓋的水膜的汽化潛熱降低了冷凝器內制冷劑的溫度,因而,壓縮機耗功量變小。當噴水量達到一定程度后,覆蓋在冷凝器表面的水膜較均勻,此后再增加噴水量,冷凝器的傳熱傳質能力不會增加,壓縮機耗功量保持不變。由圖4(b)可知,同等條件下,壓縮機的耗功量隨著進風溫度的升高而增加,且噴水時的耗功量更小。這是因為,進風溫度與冷凝器內制冷劑的傳熱溫差是冷凝器傳熱的推動力,因此,進風溫度的升高會使得壓縮機消耗更多的功。由圖4(c)可知,保持進風溫度33℃不變,壓縮機的耗功量隨著進風速度的升高而減小,且噴水時的耗功量小。不噴水時,進風速度的增加會強化空氣與冷凝器的對流換熱;噴水時,風速的增加使得空氣與水膜間的對流換熱以及傳質過程增強,達到相同的制冷效果,壓縮機耗功量減少。
3 結論
通過實驗研究得出:冷凝器是否采用噴淋均存在同一進風速度下壓縮機耗功量隨進風溫度的升高而增大;而在同一進風溫度下,壓縮機耗功量隨進風速度的增加而降低,且采用噴淋后的壓縮機能耗比不采用噴淋時有所下降。通過正交實驗結果直觀分析與方差分析得出,影響壓縮機耗功量的主次關系均為:進風溫度、噴水量、進風速度,且當進風溫度為28 ℃、進風速度為2.5 m/s、噴水量為22 L/h時,壓縮機耗功量最小,為418 W。
筆者只對選定的參數及其水平進行了研究,若要得出更為全面的研究結論,還需要另外選定參數及水平,在其他工況條件進行深入研究。
參考文獻:
[1] 鄭賢德.制冷原理與裝置[M].2版.北京:機械工業出版社,2008.
ZHENG X D.Refrigeration principle and device [M].2ed. Beijing:Machinery Industry Press,2008.(in Chinese)
[2] ALA H, KAI S R. Performance investigation of plain and finned tube evaporative cooled heat exchangers [J].Applied Thermal Engineering, 2003, 23(3):325-340.
[3] HOSOZ M, KILICARSLAN A. Performance evaluations of refrigeration systems with air-cooled, water-cooled and evaporative condensers [J].International Journal of Energy Research, 2004, 28:683-696.
[4] 莊友明.蒸發式冷凝器和水冷式冷凝器的能耗比較及經濟性分析[J].制冷,2001,20(1):48-51.endprint
ZHUANG Y M.Energy consumption comparison and economical analysis of evaporative condenser and water-cooled condenser [J].Refrigeration,2001,20(1):48-51. (in Chinese)
[5] 王少為,于立強.蒸發式冷凝器應用于戶式空調的實驗研究[J].節能,2003(3):9-12.
WANG S W, YU L Q.Experimental study on the application of evaporative condenser in residential air conditioner [J].Energy Saving,2003(3):9-12. (in Chinese)
[6] 張建一,秘文濤.工業用蒸發式和水冷式冷凝器的循環水量和能耗研究[J].制冷技術,2007,35(3):253-256.
ZHANG J Y, MI W T.Study on circulating water and energy consumption of industrial evaporative and water-cooled condensers [J].Refrigeration Technology,2007,35(3):253-256. (in Chinese)
[7] 王軍,王海霞,畢文峰.氨用制冷系統蒸發式冷凝器的能耗研究[J].制冷技術,2011,39(10):74-77.
WANG J, WANG H X,BI W F.Study on energy consumption of evaporative condenser in ammonia refrigeration system [J].Refrigeration Technology,2011,39(10):74-77. (in Chinese)
[8] ERTUNC H M,HOSOZ M. Artificial neural network analysis of a refrigeration system with an evaporative condenser [J].Applied Thermal Engineering,2006,26:627-635.
[9] ERTUNC H M,HOSOZ M. Comparative analysis of an evaporative condenser using artificial neural network and adaptive neuro-fuzzy inference system [J].International Journal of Refrigeration, 2008, 31:1426-1436.
[10] VRACHOPOULOS M G,FILIOS A E, KOTSIOVELOS G T. Incorporated evaporative condenser [J].Applied Thermal Engineering,2007, 27:823-828.
[11] WANG T W, SHENG C G, NNANNA A G A. Experimental investigation of air conditioning system using evaporative cooling condenser [J].Energy and Buildings, 2014, 81:435-443.
[12] LIU H W, ZHOU Q S, LIU Y L . Experimental study on cooling performance of air conditioning system with dual independent evaporative condenser [J].International Journal of Refrigeration,2015, 55:85-92.
[13] 朱冬生,沈家龍,唐廣棟,等.水分布對蒸發式冷凝器傳熱傳質的影響[J].工程熱物理學報,2007,28(1):83-85
ZHU D S, SHENG J L, TANG G D, et al.Effect of water distribution on heat and mass transfer in evaporative condenser [J].Journal of Engineering Thermophysics,2007,28(1):83-85. (in Chinese)
[14] 李元希,蔣翔,吳治將,等.板式蒸發式冷凝器水膜傳熱特性研究[J].武漢理工大學學報,2010,32(13):131-134.
LI Y X, JIANG X, WU Z J,et al.Study on water film heat transfer characteristics of plate evaporative condenser [J].Journal of Wuhan University of Technology,2010,32(13):131-134. (in Chinese)
[15] 高煌,張歡,由世俊,等.利用蒸發式冷凝器再生除濕溶液時傳質系數的實驗研究[J].暖通空調,2012,42(1):65-68.
GAO H,ZHANG H,YOU S J,et al.Experimental study on mass transfer coefficient of regenerative desiccant solution by evaporative condenser [J].Heating Ventilation & Air Conditioning,2012,42(1):65-68. (in Chinese)
[16] 葉軍,章立新,沈艷,等.氨蒸發式冷凝器性能測試與計算[J].大眾科技,2013,163(15):76-79.
YE J, ZHANG L X, SHENG Y,et al.Performance test and calculation of ammonia evaporative condenser [J].Popular Science and Technology,2013,163(15):76-79. (in Chinese)
[17] 李元希,蔣翔,吳治將,等.板式蒸發式冷凝器水膜傳熱特性研究[J].武漢理工大學學報,2010,32(13):131-134.
LI Y X, JIANG X, WU Z J,et al.Study on water film heat transfer characteristics of plate evaporative condenser [J].Journal of Wuhan University of Technology,2010,32(13):131-134. (in Chinese)
[18] 李元希,黃河,楊永峰,等.板式蒸發式冷凝器的性能實驗[J].制冷與空調,2011,11(4):43-48.
LI Y X, HUANG H, YANG Y F,et al.Performance experiment of plate evaporative condenser [J].Refrigeration and Air Conditioning,2011,11(4):43-48. (in Chinese)endprint