劉慧 黃凱



摘 要:本文介紹了104遙控報(bào)文的幀結(jié)構(gòu)和MMS報(bào)文的讀取方法,以一起調(diào)度主站遙控失敗案例分析如何通過解讀報(bào)文處理遙控故障,以及軟件PCS-Gateway遠(yuǎn)動(dòng)調(diào)試方法,并總結(jié)常見遙控失敗的原因,以期為今后工作的開展提供借鑒。
關(guān)鍵詞:104遙控報(bào)文;MMS報(bào)文;PCS-Gateway
中圖分類號(hào):TM63 文獻(xiàn)標(biāo)識(shí)碼:A 文章編號(hào):1003-5168(2018)17-0047-04
Analysis of Remote Control Failure of Intelligent Substation
LIU Hui HUANG Kai
Abstract: This paper introduced the frame structure of the 104 telecontrol message and the reading method of MMS message. In order to dispatch the remote control failure case of the main station, the paper analyzed how to handle the remote control failure by reading the message, and the software PCS-Gateway telecontrol debugging method, and summarized the reasons for the common remote control failure, in order to provide reference for the future work.
Keywords:104 remote control message;MMS message;PCS-Gateway
隨著越來越多智能變電站的投運(yùn)及常規(guī)變電站的改造升級(jí),智能變電站逐漸普及,變電站開關(guān)、變壓器分接頭調(diào)節(jié)、GIS刀閘等設(shè)備的操作多由調(diào)度遙控操作完成。遙控操作在優(yōu)化電網(wǎng)運(yùn)行方式、處理緊急故障事故和保障電網(wǎng)安全穩(wěn)定運(yùn)行等方面發(fā)揮著不可替代的作用。但在實(shí)際運(yùn)行過程中,遙控操作不成功的現(xiàn)象時(shí)有發(fā)生。因此,遙控操作失敗后能進(jìn)行準(zhǔn)確分析判斷,快速查找定位故障,消除隱患,使遙控操作繼續(xù)執(zhí)行顯得更加重要[1]。
1 104遙控報(bào)文
目前,主站與廠站間信息傳輸?shù)闹饕侄问蔷W(wǎng)絡(luò)通信模式,基于網(wǎng)絡(luò)通信方式的IEC60870-5-104電力網(wǎng)絡(luò)通信規(guī)約為主站與子站間進(jìn)行電力信息傳輸提供了一套完善的通信協(xié)議,因其靈活、簡(jiǎn)單、經(jīng)濟(jì)的優(yōu)勢(shì),在電力系統(tǒng)中被廣泛應(yīng)用。因此,掌握104規(guī)約對(duì)電力自動(dòng)化系統(tǒng)和設(shè)備的運(yùn)行維護(hù)有著重要意義[2]。
1.1 104遙控報(bào)文的幀結(jié)構(gòu)
104遙控報(bào)文的幀結(jié)構(gòu)如表1所示。
注:其中傳送原因:6表示激活;7表示激活確認(rèn);8表示停止激活;9表示停止激活確認(rèn);0A表示激活結(jié)束。
其中品質(zhì)描述DCO格式如表2所示。
DCO:=CP8{DCS,QOC}。
DCS:=雙點(diǎn)遙控狀態(tài),bit1--bit2。
<0>:=不允許,<1>:=OFF,開,<2>:=ON,合,<3>:=不允許。
QOC:=bit3--bit8(QU,S/E)。
QU:=遙控輸出方式,bit3--bit7<0~31>。<0>:=執(zhí)行,<1>:=選擇。
1.2 104遙控報(bào)文解析
一個(gè)完整的遙控報(bào)文流程包括4部分:遙控選擇激活、遙控選擇確認(rèn)、遙控執(zhí)行激活和遙控執(zhí)行激活確認(rèn)[3]。
主站發(fā)送遙控/遙調(diào)選擇命令(傳送原因?yàn)?,S/E=1),子站返回遙控/遙調(diào)返校(傳送原因?yàn)?,S/E=1);主站下發(fā)遙控/遙調(diào)執(zhí)行命令(類型標(biāo)識(shí)為46/47,傳輸原因?yàn)?,S/E=0),子站返回遙控/遙調(diào)執(zhí)行確認(rèn)(傳輸原因?yàn)?,S/E=0)。當(dāng)遙控/遙調(diào)操作執(zhí)行完畢后,子站返回遙控/遙調(diào)操作結(jié)束命令(傳送原因?yàn)?0,S/E=0)。
具體遙控報(bào)文解析如下。
報(bào)文:68 0E 04 00 0A 00 2E 01 06 00 01 00 01 60 00 82
解析:(遙控選擇激活)。類型標(biāo)識(shí):2EH,雙點(diǎn)遙控;可變結(jié)構(gòu)限定詞:01H,1個(gè)信息字;傳送原因:0600H,遙控激活;公共地址:0100H;信息體地址:016000H,第一個(gè)遙控點(diǎn);信息體元素:82H,即1000 0010,S/E=1,為遙控選擇,DCS=2,為遙控合。
報(bào)文:68 0E 0A 00 06 00 2E 01 07 00 01 00 01 60 00 82
解析:(遙控激活確認(rèn))子站返回遙控激活確認(rèn),傳送原因?yàn)?7。
報(bào)文:68 0E 06 00 0C 00 2E 01 06 00 01 00 01 60 00 02
解析:(遙控執(zhí)行激活)信息體元素:02H,即0000 0010,S/E=0,遙控執(zhí)行,DCS=2,遙控合。
報(bào)文:68 0E 10 00 08 00 2E 01 07 00 01 00 01 60 00 02
解析:(遙控執(zhí)行激活確認(rèn))子站返回遙控激活執(zhí)行確認(rèn),傳送原因?yàn)?7。
2 MMS報(bào)文
讀取MMS報(bào)文,主要是運(yùn)用相關(guān)軟件抓取現(xiàn)場(chǎng)通信報(bào)文,通常采用Ethereal軟件。Ethereal是一個(gè)網(wǎng)絡(luò)包的分析軟件,其可以捕獲網(wǎng)絡(luò)包,并詳細(xì)顯示出捕獲該網(wǎng)絡(luò)包所包含的數(shù)據(jù),幫助我們學(xué)習(xí)網(wǎng)絡(luò)協(xié)議,分析網(wǎng)絡(luò)問題。
運(yùn)用Ethereal軟件截取MMS報(bào)文時(shí),需要先在交換機(jī)上設(shè)定鏡像端口,把要截取報(bào)文的端口鏡像到鏡像端口,電腦只要連接到鏡像端口即可截取其他端口的報(bào)文。
Ethereal軟件菜單欄及功能如圖1所示。
點(diǎn)擊啟動(dòng)監(jiān)視報(bào)文后,會(huì)彈出如圖2所示的對(duì)話框。檢查設(shè)置無誤后就可以對(duì)報(bào)文進(jìn)行監(jiān)視。
在軟件菜單欄界面可以點(diǎn)擊“Capture Options”捕獲選項(xiàng)對(duì)話框設(shè)置,設(shè)置字段對(duì)話框如圖3所示。
設(shè)置完成后點(diǎn)擊start可讀取到鏡像端口的所有報(bào)文。由于報(bào)文數(shù)量大,刷新速度快,檢索復(fù)雜,可在過濾器中輸入報(bào)文類型“mms”,即可檢索到MMS報(bào)文。
3 案例分析
主站對(duì)某子站進(jìn)行遙控,子站未正確返校,遙控失敗。連接子站數(shù)據(jù)通信網(wǎng)關(guān)機(jī),監(jiān)視到啟動(dòng)及總召報(bào)文傳輸正常,進(jìn)行主站遙控,提示返回失敗,對(duì)截取到的報(bào)文進(jìn)行如下解析。
報(bào)文:68 0E 0E 00 30 00 2D 01 06 00 01 00 01 60 00 80
解析:數(shù)據(jù)單元長(zhǎng)度=14,I格式,發(fā)送序號(hào)(NS)=7,接收序號(hào)(NR)=24;VSQ=1(SQ=0 INFONUM=1),COT=6(T=0 PN=0 CAUSE=6),COA=1;主站單點(diǎn)遙控激活,公共地址0001H,信息體地址6001H,信息體元素:80H,即為1000 0000H,其中S/E=1,為遙控選擇,DCS=0,遙控狀態(tài)為不允許[4]。
報(bào)文:68 0E 30 00 10 00 2D 01 47 00 01 00 01 60 00 80
解析:數(shù)據(jù)單元長(zhǎng)度=14,I格式,發(fā)送序號(hào)(NS)=24,接收序號(hào)(NR)=8;VSQ=1(SQ=0 INFONUM=1),COT=71(T=0 PN=1 CAUSE=7),COA=1;子站單點(diǎn)遙控激活確認(rèn),公共地址0001H,信息體地址6001H,信息體元素:80H,即為1000 0000H,其中S/E=1,為遙控選擇,DCS=0,遙控狀態(tài)為不允許。
104遙控報(bào)文中只顯示遙控結(jié)果,不能解析出失敗原因,因此還需要讀取MMS報(bào)文。通過Ethereal截取到的MMS報(bào)文中有一條測(cè)控發(fā)給數(shù)據(jù)通信網(wǎng)關(guān)機(jī)的報(bào)文為Unconfirmed:InformationReport,如圖4所示。其中AccessResults顯示DATA Access Error:type-inconsistent(7)7,遙控類型錯(cuò)誤,檢查數(shù)據(jù)通信網(wǎng)關(guān)機(jī)中的轉(zhuǎn)發(fā)點(diǎn)表,該遙控點(diǎn)配置是雙點(diǎn)遙控[5]。但通過解析104遙控報(bào)文可知,主站進(jìn)行遙控時(shí)選擇的是單點(diǎn)遙控,因此遙控失敗。
主站再次對(duì)該遙控點(diǎn)進(jìn)行遙控,選擇雙點(diǎn)遙控(或者修改數(shù)據(jù)通信網(wǎng)關(guān)機(jī)中轉(zhuǎn)發(fā)點(diǎn)表的遙控點(diǎn)配置,主子站保持一致即可),返回選擇正確,選擇“執(zhí)行”后,遙控執(zhí)行成功,104報(bào)文如下[6]:
68 0E 04 00 0A 00 2E 01 06 00 01 00 01 60 00 82→主站雙點(diǎn)遙控激活
68 0E 01 00 06 00 2E 01 07 00 01 00 01 60 00 82→子站返回雙點(diǎn)遙控激活確認(rèn)
68 0E 06 00 0C 00 2E 01 06 00 01 00 01 60 00 02→主站執(zhí)行雙點(diǎn)遙控激活
68 1A 0C 00 08 00 01 04 03 00 01 00 03 00 00 01 04 00 00 01 05 00 00 01 06 00 00 01→子站執(zhí)行遙控命令后變位信息上送
4 運(yùn)用PCS-Gateway調(diào)試
4.1 PCS-Gateway遠(yuǎn)動(dòng)調(diào)試軟件
PCS-Gateway軟件是一款遠(yuǎn)動(dòng)調(diào)試軟件,通過該軟件可以查看數(shù)據(jù)通信網(wǎng)關(guān)機(jī)的配置、各通道連接狀態(tài)和通信信息。PCS-Gateway軟件主界面如圖5所示。
使用PCS-Gateway軟件調(diào)試遠(yuǎn)動(dòng)時(shí),將裝有該軟件的調(diào)試機(jī)用網(wǎng)線與數(shù)據(jù)通信網(wǎng)關(guān)機(jī)相連,點(diǎn)擊“調(diào)試”菜單下的開始,在界面下方的事件輸出列表中會(huì)提示“管理機(jī)已連接”與“連接管理機(jī)成功,進(jìn)入調(diào)試模式”[7]。在規(guī)約配置中選擇對(duì)應(yīng)的通道,可以讀出該通道傳輸?shù)木唧w信息。
4.2 失敗信息分析
圖6為檢同期閉鎖遙控,遙控失敗的通信信息。
從圖6可以看出,主站下發(fā)雙點(diǎn)遙控選擇命令后,子站返校成功,主站下發(fā)執(zhí)行命令,子站否定響應(yīng),由檢同期閉鎖遙控,遙控失敗。當(dāng)檢同期條件滿足后再進(jìn)行遙控,遙控成功。
圖7為數(shù)據(jù)通信網(wǎng)關(guān)機(jī)中應(yīng)用層地址配置錯(cuò)誤,導(dǎo)致遙控失敗的信息圖片。
從圖7可以看出,子站數(shù)據(jù)通信網(wǎng)關(guān)機(jī)的配置中應(yīng)用層地址配置為3,而實(shí)際為1,因此,雙點(diǎn)遙控命令子站否定響應(yīng),遙控失敗。修改并重新下裝正確配置后,主站遙控成功。
圖8為調(diào)度主站操作指令與該遙控點(diǎn)實(shí)際位置不對(duì)應(yīng),出現(xiàn)“分控分”導(dǎo)致遙控失敗的信息圖片。
從圖8可以看出,引用表為空,調(diào)度主站操作指令與該遙控點(diǎn)實(shí)際位置不對(duì)應(yīng)。經(jīng)核查,主站的操作指令是控分,該遙控點(diǎn)在主站端的位置也是分位。因此,遙控命令子站否定響應(yīng),遙控失敗。當(dāng)主站端選擇控合,遙控成功[8]。
圖9為數(shù)據(jù)通信網(wǎng)關(guān)機(jī)把手打至禁止遙控位置,導(dǎo)致遙控失敗的信息圖片。
從圖9可以看出,遙控失敗信息“l(fā)ocal state error”即本地狀態(tài)不對(duì)。經(jīng)檢查,數(shù)據(jù)通信網(wǎng)關(guān)機(jī)的禁止/允許遠(yuǎn)方遙控把手切至禁止遠(yuǎn)方遙控位置,因此,遙控命令子站否定響應(yīng),遙控失敗。把手打至允許遠(yuǎn)方遙控位置后,主站進(jìn)行遙控時(shí),遙控成功。
4.3 遙控失敗原因總結(jié)
智能變電站常見遙控失敗的原因主要有以下幾方面。
4.3.1 主站與廠站未連接。例如,數(shù)據(jù)通信網(wǎng)關(guān)機(jī)配置錯(cuò)誤,IP地址、RTU地址、端口號(hào)、實(shí)例號(hào)錯(cuò)誤和實(shí)例號(hào)沖突;調(diào)度主站IP地址、RTU地址、端口號(hào)等公共地址參數(shù)配置錯(cuò)誤;或數(shù)據(jù)通信網(wǎng)關(guān)機(jī)故障,內(nèi)部程序出錯(cuò)。
4.3.2 遠(yuǎn)動(dòng)遙控轉(zhuǎn)發(fā)表配置錯(cuò)誤。例如,轉(zhuǎn)發(fā)表順序配置錯(cuò)誤或?qū)傩耘渲缅e(cuò)誤,起始信息體地址錯(cuò)誤,調(diào)度主站遙控點(diǎn)表配置與遠(yuǎn)動(dòng)遙控轉(zhuǎn)發(fā)表配置不一致等。
4.3.3 遙控條件不滿足。主要表現(xiàn)在以下幾方面。①調(diào)度主站操作指令與遙控對(duì)象位置不對(duì)應(yīng),出現(xiàn)“合控合、分控分”現(xiàn)象[9]。②數(shù)據(jù)通信網(wǎng)關(guān)機(jī)在接受調(diào)度主站遙控預(yù)置時(shí)未校驗(yàn)到測(cè)控裝置,導(dǎo)致出現(xiàn)預(yù)置成功,但執(zhí)行不成功。③數(shù)據(jù)通信網(wǎng)關(guān)機(jī)的禁止/允許遠(yuǎn)方遙控切至禁止遠(yuǎn)方遙控位置,遙控命令未下發(fā)至測(cè)控裝置。④測(cè)控裝置的遠(yuǎn)方/就地把手切至就地位置,且測(cè)控裝置對(duì)選擇命令的返校不檢查遠(yuǎn)方/就地位置,導(dǎo)致遠(yuǎn)方遙控執(zhí)行不成功。⑤測(cè)控裝置CPU、開出功能和通信光纖等存在異常,未發(fā)出正確的控制報(bào)文。⑥測(cè)控裝置與智能終端之間通信存在異常,導(dǎo)致智能終端未能收到測(cè)控裝置發(fā)出的控制報(bào)文;測(cè)控裝置與智能終端之間的虛端子連線錯(cuò)誤,導(dǎo)致實(shí)際動(dòng)作的一次設(shè)備不是該遙控對(duì)象。⑦智能終端故障,導(dǎo)致操作無法開出;智能終端與遙控對(duì)象機(jī)構(gòu)之間的回路問題,如遙控出口壓板未投入、操作電源消失,導(dǎo)致執(zhí)行不成功;遙控對(duì)象機(jī)構(gòu)問題,如控制切至就地位置、機(jī)構(gòu)閉鎖或機(jī)構(gòu)故障。⑧檢同期不滿足條件[10]。
遙控失敗的原因有很多,查找原因的方法和手段也多種多樣。在實(shí)際工作中,可以將讀取解析報(bào)文和工程調(diào)試軟件如PCS-Gateway結(jié)合起來使用,從而取得事半功倍的效果。
遙控操作的可靠性對(duì)電網(wǎng)安全穩(wěn)定運(yùn)行起著重要作用。在實(shí)際工作中,應(yīng)分析總結(jié)遙控操作常見故障,對(duì)典型案例進(jìn)行重點(diǎn)分析和學(xué)習(xí),從各個(gè)環(huán)節(jié)研究故障處理方法,為及時(shí)處理遙控操作中遇到的各種問題奠定基礎(chǔ),提高遙控操作正確率,確保電網(wǎng)安全穩(wěn)定運(yùn)行。
參考文獻(xiàn):
[1]王首頂,韓福坤,徐正山.IEC60870-5系列協(xié)議應(yīng)用指南[M].北京:中國電力出版社,2008.
[2]王順江,施毅斌,王洪哲.電力自動(dòng)化通訊規(guī)約精解[M].沈陽:東北大學(xué)出版社,2014.
[3]周華良,鄭玉平,姚吉文.面向智能變電站二次設(shè)備的網(wǎng)絡(luò)報(bào)文管控技術(shù)[J].電力系統(tǒng)自動(dòng)化,2015(39):96-100.
[4]李沖.智能變電站網(wǎng)絡(luò)報(bào)文快速分析處理研究[D].濟(jì)南:山東大學(xué),2015.
[5]竇中山,魏勇,王興安.智能變電站網(wǎng)絡(luò)報(bào)文分析關(guān)鍵技術(shù)研究[J].電氣技術(shù),2014(6):96-99.
[6]李莉,鄧叢林,何易.水電站遠(yuǎn)動(dòng)通信規(guī)約簡(jiǎn)介[J].水電站設(shè)計(jì),2009(1):22-24.
[7]楊特寧.周期性遙控拒動(dòng)故障的分析與處理[J].電工技術(shù),2016(7):97-98.
[8]韓小軍,蔡?hào)|升,黃琦,等.基于IEC104遠(yuǎn)動(dòng)規(guī)約的智能變電站輔助平臺(tái)測(cè)試系統(tǒng)設(shè)計(jì)與實(shí)現(xiàn)[J].電測(cè)與儀表,2014(14):104-109.
[9]李振甲,劉建英.電力通信規(guī)約[M].北京:北京理工大學(xué)出版社,2014.
[10]林冶,張孔林,唐志軍.智能變電站二次系統(tǒng)原理與現(xiàn)場(chǎng)實(shí)用技術(shù)[M].北京:中國電力出版社,2016.