Modelling of Commercial Grid-Connected PV Inverters Based on Transient Analysis and System Identification

2021-05-27 14:29:38WengGongyuMaoMeiqinZhangLiuchenNikosHatziargyriou
電工技術學報 2021年10期
關鍵詞:方法模型系統

Weng Gongyu Mao Meiqin Zhang Liuchen,2 Nikos Hatziargyriou

Modelling of Commercial Grid-Connected PV Inverters Based on Transient Analysis and System Identification

111,23

(1. Research Center for Photovoltaic System Engineering MOE Hefei University of Technology Hefei 230009 China 2. School of Electrical and Computer Engineering University of New Brunswick Fredericton E3B5A3 Canada 3. School of Electrical and Computer Engineering National Technical University of Athens Athens 15780 Greece)

The modelling of grid-connected photovoltaic (PV) generation systems is the basis for studying their interaction with the grid. The transients of PV systems are determined by weather and grid conditions, as well as the characteristics of commercial inverters, whose topology and control algorithm are usually unknown. This hinders the analysis of the impacts that PV systems might have on the grid. For this purpose, a generic process for modelling PV systems based on transient analysis and system identification is presented. By viewing a PV system as a black-box without knowledge of its internal components, structure or control algorithm, the model was established through measured input-output data and system identification. Transfer functions were taken as the model structure based on classic control theories. A power hardware-in-the-loop system was used to verify the process by collecting instantaneous input-output data from the terminals of a commercial 3kW PV inverter. The results show that the developed model reproduces accurately the transients of the inverter under various disturbances, demonstrating the effectiveness of this generic modelling process.

PV inverter modelling, system identification, transfer function, power-hardware-in- the-loop (PHIL)

0 Introduction

Photovoltaic generation systems have become widely installed around the world in recent years. As the penetration of grid-connected PV generation systems increases, the volatility of their power production pose challenges to the stable operation of the grid[1-2]. Power system planners, utility engineers, and PV system developers often need to model and simulate distribution systems to investigate the behaviours of PV systems and their potential impacts on the grid[3-4]. Therefore, it is necessary to establish reliable and accurate models of grid-connected PV systems to investigate the operational characteristics of the PV and the grid.

The output of the PV systems is mainly controlled through their interfacing inverters. In practical operations, the operating conditions constantly change due to variation of irradiance, temperatures, and grid conditions. In most cases, the behaviour of inverters is primarily considered in a steady state with slowly changing working con- ditions[5]. However, in many cases, conditions change abruptly, for example, sudden changes of irradiation by passing clouds, load changes in the grid caused by nearby grid failures. Under these circumstances, PV inverters operate in a transient state and will probably bring challenges to the stable operation of the system[6-7]. Thus, the transient conditions of a PV system are mainly investigated in this paper.

The modelling of power electronic system is usually divided into three levels according to the analysis purposes, i.e. the component level, converter level and system level[5]. Component level models are developed to simulate detailed circuits at the level of power diodes, inductors, and capacitors. For converter level modelling, models are developed to represent the average behaviour and the switching characteri- stics of the converters[8-10]. While these models are reliable and accurate, large amount of computational time is needed when analysing large power electronic systems. At the same time, due to confidentiality reasons, system integrators are usually unable to get details about the converters. Besides, there are various control algorithms developed to tackle with different scenarios[11-13], which also limits the usage of these kinds of models. System-level models, however, based on input and output measurements, have gained attention recently[14-19]. For system-level modelling, power converters are considered as black-boxes without knowledge of their physical structure. Take the black-box-parameter model proposed in the 1980s as an example[14-18]. The model is composed of several virtual dynamic systems, whose parameters were identified through either AC-sweep in the frequency domain[14]or transient analysis in the time domain[15-18]. Since details of commercial PV inverters are proprietary and mostly very limited, a system-level model is further investigated in this paper.

While the-parameter model only focuses on the converters itself, the output of the grid-connected PV system depends also on the external weather and the grid conditions. Thus, a black-box model for the whole integrated PV system is required to study the overall features.

In summary, a new generalized modelling process based on system identification for system- level analysis of grid-connected PV systems is presented in this paper. The inputs of the model were selected by analysing the factors influencing the output power of the system. After that, different amplitude disturbances were conducted at each input of the model. The transient responses were measured and the system transfer functions from the inputs to the output were identified through system identification. Such a model is useful to simulate the transient interactions between PV systems and the grid. It enables utility planners to conduct the necessary studies before connecting PV units to the grid. The features of this modelling process are summarized as follows:

(1) This is a unified, general modelling process because no explicit knowledge of the PV inverter composition or its control methods is required.

(2) The model reflects accurately the output electrical characteristics of the inverter within the range of 10%~100% of rated power.

(3) The modelling process is carried out offline. The parameters of the model are identified by transient data to accurately represent the behaviours of the PV system under different transients.

Power hardware-in-the-loop (PHIL) testing[20-21]on PV systems with the same functionalities provides a valuable tool to measure the transient responses of such systems. Transient experiments were designed and carried out.

1 Model Structure

A simplified diagram of a PV system is shown in Fig.1[22]. The main features of this system are:

(1) The output power of the PV panels is determined by weather conditions such as irradiation, temperature, and by the power reference of the inverter control system. Note that when the value of the active power reference is higher than the maximum power point (MPP) of the PV panel, the system cannot follow the reference power but produce the MPP powermpp, which is determined by irradiation and temperature. While when the value of the active power reference is lower than the MPP power, the system will produce according to the power reference. Thus, a comparison between the value of MPP power and power reference should be made before calculating the output power of the model.

Fig.1 Simplified diagram of a PV system

(2) When the voltage of the grid fluctuates, the output power of the inverter will fluctuate as well.

(3) As the PV system operates as a current source, its output voltage is set and maintained by the grid. The transients of the PV system are reflected in the current fed into the grid. Thus, the output current of the system is mainly studied. Once the current is known, the active and reactive power of the system can be readily obtained.

Based on these considerations, the black-box model of the single-phase PV system proposed in this paper is shown in Fig.2. The inputs of the system are the solar irradiation, the active power reference*, the temperatureand the instant value of the grid voltageg. The AC side currentof the inverter is taken as the output. Besides, a comparison block takes in the irradiation, power reference and temperature and output the result to the PV system block.

Fig.2 Black-box model of the PV system

Fig.3 Simplified one-line diagram of a general single-phase current-controlled PV inverter

Fig.4 Block diagram of the inverter grid current control loop

From Fig.4, the closed-loop response of the current control loop can be derived as

wherecli() andoi() are the current reference to output transfer function and closed-loop output admittance, respectively.c() is the open-loop gain of the current control loop, which is given by

wherec() is the PR current controller.iandoare the transfer functions of the LCL-filter plant as shown in

whereZf(),Zg() andZf()denote the impedances of the LCL-filter inductors and capacitor, respectively.o() is also the open-loop output admittance.

Fig.5 Block diagram of the black-box PV system

Note that the influence of the temperature on the output of the system is little. Besides, the temperature is not likely to change abruptly, thus, the transfer- function-effect of the temperature on the output is neglected in the model. While the temperature does influence the output power, It is kept as one of the independent variables when calculatingmpp, as its contribution to the output of the system.

Tab.1 The results of Pmpp and h

2 Modelling Process of The PV System

A disturbance-observation process was conducted to identify the transfer functions in equation (7). Disturbances were conducted and the corresponding output currentwas measured in the laboratory set-up shown in Fig.6, corresponding to the three targetss,p*andoi, respectively.

The disturbance upon each input and the corresponding currentwere used to identifying the transfer functions. More specifically:

(3)先內業后外業的采集模式。立體采集分為先內后外、先外后內、內外采編一體化三種方式,不動產線劃圖采用先內業定位、外業定性的采集模式,需要保證內業定位精準無誤,盡可能較少外業工作量;同時外業定性核查內業采集數據,為內業提供準確的屬性信息。

(3) When identifying each transfer function, different magnitudes of step disturbances were conducted. The data obtained in each magnitude disturbance is used to train the model corresponding to this magnitude disturbance. While the model developed should be validated by the other magnitudes data.

(4) The details of the transfer functions to be identified in equation (7) are shown from equation (8) to equation (10). The identification is more of a trial-and-error process where one estimates the parameters of various model orders and compares the results against the measured data.

For an example, take the parameters ofs() shown in

whereandare the orders of denominator and numerator of the transfer function, respectively.b,b1, …,0are the polynomial coefficients of the transfer function numerator.a1,a2, …,0are the polynomial coefficients of the denominator. These are the parameters to be identified. As the ordersandwere integers, they were not identified but were set manually at different values, after which the coefficients of the transfer function were identified and the results of the model were obtained, based on which the optimal orders were compared and determined.

(5) The initialization and identification of the parameters were carried out using the system identification toolbox in Matlab. More specifically, one of the following three different initial conditions were selected during estimation, etc., all initial conditions are taken as zero, the necessary initial conditions are treated as estimation parameters, the necessary initial conditions are estimated by a backward filtering process. After that, different algorithms were used to initialize the values of the numerator and denominator. These algorithms include the instrument variable approach, state variable filters approach, generalized Poisson moment functions approach, et al, which are all widely used in this field[24-25]. A comparison of the results of these initial conditions and algorithms was made and the method that yields the least prediction error norm was selected.The Levenberg-Marquardt (LM) algorithm was then adopted for the parameters iterative estimation. This algorithm has become a standard technique for least-squares problems and can be thought of as a combination of the gradient-descent and the Gauss-Newton (GN) method[26]. The LM method acts more like a gradient-descent method when the parameters are far from their optimal value and more like the GN method when the parameters are closer[27]. As there are two possible options at each iteration, the LM is faster to converge than either the gradient descent or the GN on its own. Another advantage is that the algorithm can find a solution, even when the initial guess is far from the optimal point[28]. These features make the LM algorithm efficient to update the parameters of the transfer function. The flow chart of the Levenberg-Marquardt algorithm is shown in Fig.7[29].

Fig.7 Flow chart of the Levenberg-Marquardt algorithm

The fitting rate of the identification results of the transfer function is defined byfitas shown in

whereis the measured output of the inverter,is the input of the model,is the amount of the data used. Transfer functions with a fitting rate higher than 85% are considered able to reproduce the transient accurately.

The model development and validation[30]process are shown in Fig.8.

Fig.8 Model development and validation process

3 Results and Validation of the Model

3.1 Experiment Platform Configuration

The power hardware-in-the-loop PV system shown in Fig.9 was used for modelling and validating the system. The PV inverter under test was an SMA Sunny Boy SB 3000TL-21 with a DC side MPP voltage range from 175V to 500V. The output of the PV simulator was set at 400V, at a maximum power point of 2kW, corresponding to solar irradiation of 1 000W/m2. Thus, the PV simulator can be connected directly to the inverter without the need for a step-up converter. A resistive load of 2kW absorbs the active power of the 2kV·A PV. The AC voltage supply set by the RTDS was at 230V, 50Hz (as this experiment was conducted in Greece). The available disturbance ranges of each input are shown in Tab.2.

Fig.9 The Power hardware-in-the-loop experiment system

Tab.2 The available disturbance ranges of each variables

3.2 Model Results Analysis

Fig.10 Example training data of and current response when irradiation steps

Corresponding to each of these disturbance processes, transfer functions were identified through trial-and-error until the best was found. After that, this transfer function was validated by the data of the other magnitude of disturbances. It will be taken as thesif it represents these processes accurately as well.

The transfer function identified corresponds to the disturbance of “800W/m2to 1 000W/m2” is with the best fitness. The results against the irradiation disturbance processes are shown in Fig.11. The average fitting rate reaches more than 85%. Thus, it was taken as the transfer functions, as shown in equation (14).

Fig.11 The fitness of Gs against different irradiation disturbance processes

Similarly, transfer functions with high accuracy corresponding to the active power disturbance from “300W to 2 000W” and the grid voltage disturbance from “215V to 235V” were found, respectively. The fitness of these transfer functions is shown in Fig.12 and Fig.13. The average accuracy also reaches more than 85%. Thus, they were taken as the transfer function ofp*andoi, as shown in equation (15) and equation (16). Equation (14) to equation (16) are regarded as the general model of the PV system.

Fig.12 The fitness of Gp* against different active power reference disturbance processes

Fig.13 The fitness of Yoi against different grid voltage disturbance processes

3.3 Validation of the Model

To validate these identified transfer functions, the current responses when applying the same disturbance to the identified model and the inverter were compared. Take one of the results in each case shown as follows. In Fig.14, the current increases along with solar irradiation steps up from “800W/m2to 1 000W/m2”. In Fig.15, the current increases as the active power reference steps up from “1 800W to 2 000W”. In Fig.16, the current decreases along with the voltage step up from “230V to 240V” as the PV inverter trying to maintain the output active power. As we can see, the model fits the data well in these situations, proving the effectiveness of the presented modelling process.

Fig.14 Output current comparison of the inverter and the identified model when solar irradiation steps

Fig.15 Output current comparison of the inverter and the identified model when active power reference steps

Fig.16 Output current comparison of the inverter and the identified model when grid voltage steps

4 Conclusion

A single-phase grid-connected PV inverter was modelled through transient analysis and system identi- fication. Solar irradiation, active power reference and grid voltage were taken as the inputs of the model, the AC side current of the inverter was taken as the output. Three experiment cases corresponding to each of the input were carried out. Transfer functions with high fitness were identified correspondingly, which can accurately reproduce the transients of the disturbances processes within the operating range of the inverter. This good agreement between the model output and the inverter response validates both the black-box model theory and the system identification method.

Acknowledgment:The authors gratefully acknow- ledge the SmartRUE research team of the National Technical University of Athens in Greece for their help and support of the PHIL experiment system. The authors also would like to appreciate the China Scholarship Council for the funding with the grant number of 201706690020 and the grant supported by the 111 Project.

[1] Tobnaghi D. A review on impacts of grid-connected PV system on distribution networks[J]. International Journal of Electrical, Computer, Energetic, Electronic and Communication Engineering, 2016, 10(1): 137- 142.

[2] Eftekharnejad S, Vittal V, Heydt G T, et al. Impact of increased penetration of photovoltaic generation on power systems[J]. IEEE Transactions on Power System, 2013, 28(2): 893-901.

[3] Ellis A, Behnke M, Elliott R. Generic solar photo- voltaic system dynamic simulation model specifi- cation[R]. Sandia Report, Sandia National Laborato- ries, Albuquerque, New Mexico, 2013: 8-10.

[4] Ramasubramanian D, Yu Z, Ayyanar R, et al. Converter model for representing converter interfaced generation in large scale grid simulations[J]. IEEE Transactions on Power System, 2017, 32(1): 765-773.

[5] Abbood H, Benigni A. Data-driven modeling of a commercial photovoltaic microinverter[J]. Modelling and Simulation in Engineering, 2018: 5280681.

[6] Patsalides M, Efthymiou V, Stavrou A, et al. A generic transient PV system model for power quality studies[J]. Renewable Energy, 2016, 89(1): 526-542.

[7] Pourbeik P, Sanchez-Gasca J, Senthil J, et al. Generic dynamic models for modelling wind power plants and other renewable technologies in large-scale power system studies[J]. IEEE Transactions on Energy Conversion, 2017, 32(3): 1108-1116.

[8] Liu Wenjun, Zhou Long, Chen Jian, et al. Control method for grid-connected inverter with LCL filter by employing dual current closed-loops[J]. Power System Protection and Control, 2016, 44(17): 52-57.

[9] Zhang Xiao, Tan Li, Xian Jiaheng, et al. Predictive current control algorithm for grid-connected inverter with LCL filter[J]. Transactions of China Electro- technical Society, 2019, 34(S1): 189-201.

[10] Su Xiaofang, Yuan Jiaxin, Xue Gang, et al. An immune-algorithm-based dead-time elimination hybrid space vector PWM control strategy in a three-phase inverter[J]. Transactions of China Electrotechnical Society, 2016, 31(16): 135-144.

[11] Zhou Leming, Luo An, Chen Yandong, et al. A single-phase grid-connected power control and active damping optimization strategy with LCL filter[J]. Transactions of China Electrotechnical Society, 2016, 31(6): 144-154.

[12] Ren Zipan, Lu Baochun, Zhao Yalong, et al. Research on modeling and simulation of photovoltaic virtual synchronous generator[J]. Power System Protection and Control, 2019, 47(13): 92-99.

[13] Dong Runnan, Liu Shi, Liang Geng, et al. Research on control method of special inverter in micro-grid based on model predictive control[J]. Power System Protection and Control, 2019, 47(21): 11-20.

[14] Cvetkovic I, Boroyevich D, Mattavelli P, et al. Unterminated small-signal behavioral model of DC-DC converters[J]. IEEE Transactions on Power Electronics, 2013, 28(4): 1870-1879.

[15] Raga C, Barrado A, Lázaro A, et al. Black-box model, identification technique and frequency analysis for pem fuel cell with overshooted transient response[J]. IEEE Transactions on Power Electronics, 2014, 29(10): 5334-5346.

[16] Valdivia V, Lazaro A, Barrado A, et al. Black-box modeling of three-phase voltage source inverters for system-level analysis[J]. IEEE Transactions on Industrial Electronics, 2012, 59(9): 3648-3662.

[17] Valdivia V, Barrado A, Lázaro A, et al. Black-box behavioral modeling and identification of DC-DC converters with input current control for fuel cell power conditioning[J]. IEEE Transactions on Indu- strial Electronics, 2013, 61(4): 1891-1903.

[18] Valdivia V, Todd R, Bryan F J, et al. Behavioral modeling of a switched reluctance generator for aircraft power systems[J]. IEEE Transactions on Industrial Electronics, 2013, 61(6): 2690-2699.

[19] Alqahtani A, Alsaffar M, El-Sayed M, et al. Data- driven photovoltaic system modeling based on nonlinear system identification[J]. International Journal of Photoenergy, 2016: 2923731.

[20] Kotsampopoulos P C, Lehfuss F, Lauss G F, et al. The limitations of digital simulation and the advantages of PHIL testing in studying distributed generation provision of ancillary services[J]. IEEE Transactions on Industrial Electronics, 2015, 62(9): 5502-5515.

[21] Maniatopoulos M, Lagos D, Kotsampopoulos P, et al. Combined control and power hardware in-the-loop simulation for testing smart grid control algorithms[J]. IET Generation, Transmission & Distribution, 2017, 11(12): 3009-3018.

[22] Kouro S, Leon J I, Vinnikov D, et al. Grid-connected photovoltaic systems: an overview of recent research and emerging PV converter technology[J]. IEEE Industrial Electronics Magazine, 2015, 9(1): 47-61.

[23] Wang X, Blaabjerg F, Wu W. Modeling and analysis of harmonic stability in an AC power-electronics- based power system[J]. IEEE Transactions on Power Electronics, 2014, 29(12): 6421-6432.

[24] Ljung L. Experiments with identification of conti- nuous time models[J]. IFAC Proceedings Volumes, 2009, 42(10): 1175-1180.

[25] Garnier H, Mensler M, Richard A. Continuous-time model identification from sampled data: implementa- tion issues and performance evaluation[J]. Inter- national Journal of Control, 2003, 76(13): 1337- 1357.

[26] Lourakis M. A brief description of the Levenberg- Marquardt algorithm implemented by levmar[J]. Foundation of Research and Technology, 2005, 4(1): 1-6.

[27] Gavin H. The Levenberg-Marquardt method for nonlinear least squares curve-fitting problems[C]// Department of Civil and Environmental Engineering, Duke University, 2011: 1-15.

[28] Nelles O. Nonlinear system identification: from classical approaches to neural networks and fuzzy models[M]. Berlin: Springer Science & Business Media, 2013.

[29] Yu H, Wilamowski B M. Levenberg-Marquardt training[J]. Industrial Electronics Handbook, 2011, 5(12): 8-13.

[30] Pourbeik P. Model user guide for generic renewable energy system models[J]. Electric Power Research Institute, 2015: 3002006525.

基于暫態分析和系統辨識的光伏并網逆變器建模

翁公羽1茆美琴1張榴晨1,2Nikos Hatziargyriou3

(1. 合肥工業大學教育部光伏系統工程研究中心 合肥 230009 2. 加拿大新布倫瑞克大學 弗雷德里克頓 E3B5A3 3. 希臘雅典國立理工大學電氣與計算機工程學院 雅典 15780)

建立并網光伏發電系統的模型是研究其與電網交互過程的基礎。光伏系統的暫態特性不僅受天氣情況、電網工況等環境因素的影響,還取決于商用逆變器的內部結構以及控制策略,然而它們并不對外公開,這給系統的分析帶來了困難。為了解決這個問題,該文提出一種基于暫態分析和系統辨識的光伏并網逆變器通用建模方法。將光伏逆變器視作內部結構以及控制算法未知的黑箱,通過先后施加擾動和測取響應并結合系統辨識的方法來建立其模型。以一個3kW的商用光伏逆變器為研究對象,搭建硬件在環實驗系統來研究并驗證這一建模方法。結果顯示,在多種擾動對應的暫態過程中,模型的輸出均準確地擬合了逆變器的實際輸出,證明了這一建模方法的有效性。

光伏逆變器建模 系統辨識 傳遞函數 功率硬件在環

TM464

10.19595/j.cnki.1000-6753.tces.200276

This work is partially supported by the Natural Science Foundation of China (51677050) and the China Scholarship Council.

March 19, 2020;

May 25, 2020.

Weng Gongyu male, born in 1992, master degree candidate. Major interests include modelling and testing of photovoltaic generation system, system identification.E-mail: wgongyu92@163.com

Mao Meiqin female, born in 1961, associate professor, M.S. advisor. Major interests include precision and super-precision measurement, modeling and control for electromechanical system.E-mail: mmqmail@163.com (Corresponding author)

(編輯 陳 誠)

猜你喜歡
方法模型系統
一半模型
Smartflower POP 一體式光伏系統
工業設計(2022年8期)2022-09-09 07:43:20
WJ-700無人機系統
ZC系列無人機遙感系統
北京測繪(2020年12期)2020-12-29 01:33:58
重要模型『一線三等角』
重尾非線性自回歸模型自加權M-估計的漸近分布
連通與提升系統的最后一塊拼圖 Audiolab 傲立 M-DAC mini
3D打印中的模型分割與打包
用對方法才能瘦
Coco薇(2016年2期)2016-03-22 02:42:52
四大方法 教你不再“坐以待病”!
Coco薇(2015年1期)2015-08-13 02:47:34
主站蜘蛛池模板: 美女视频黄又黄又免费高清| 日韩小视频在线观看| 欧美日韩福利| 夜夜爽免费视频| 这里只有精品国产| 亚洲综合网在线观看| 国产浮力第一页永久地址| AV片亚洲国产男人的天堂| 曰AV在线无码| 国产办公室秘书无码精品| av在线人妻熟妇| 亚洲精品无码抽插日韩| 国产国产人在线成免费视频狼人色| 一边摸一边做爽的视频17国产 | 三级欧美在线| 在线无码九区| 亚洲精品久综合蜜| 午夜国产大片免费观看| 日韩精品一区二区三区免费在线观看| 亚洲欧洲日韩综合色天使| 九九热精品视频在线| 成人韩免费网站| 亚洲成a人在线观看| 国产欧美日韩18| 亚洲精品无码高潮喷水A| 天堂成人av| 国产在线视频福利资源站| 中文字幕日韩视频欧美一区| 国产成人精品第一区二区| 日本亚洲欧美在线| 国产日韩丝袜一二三区| 亚洲一级毛片在线观播放| 青青青国产视频| 欧美色伊人| 日本亚洲最大的色成网站www| 欧美日韩高清| 六月婷婷激情综合| 中国国产一级毛片| 97视频免费在线观看| 久久99国产综合精品1| 国产高清免费午夜在线视频| 一区二区三区四区精品视频| 欧美国产日韩在线观看| 精品久久久久成人码免费动漫| 国产精品偷伦视频免费观看国产| 97se亚洲综合在线韩国专区福利| 伊人91视频| 亚欧成人无码AV在线播放| 亚洲日本中文字幕天堂网| 亚洲欧美在线看片AI| 欧美精品在线视频观看| 天天综合网色中文字幕| 日本精品αv中文字幕| 综合色88| 国产乱子伦精品视频| 有专无码视频| 久久精品无码国产一区二区三区| 国产日韩精品一区在线不卡| 亚洲成a人片| 日本免费一区视频| 91黄视频在线观看| 色欲不卡无码一区二区| 99精品视频在线观看免费播放| 精品久久香蕉国产线看观看gif| 极品国产一区二区三区| 在线视频97| 精品视频福利| 日韩精品一区二区三区免费| 久久情精品国产品免费| 91精品啪在线观看国产60岁| 亚洲综合天堂网| 青草视频网站在线观看| 久久99精品久久久大学生| 拍国产真实乱人偷精品| 国产女人18毛片水真多1| 国产无码高清视频不卡| 国产玖玖玖精品视频| 91久久精品国产| 波多野结衣一区二区三区88| 国产人在线成免费视频| 国产精品青青| 国产福利不卡视频|